Inputs changed: calculate again to refresh.
Voltage lost
Estimated load voltage
Total resistive heat loss
One-way conductor resistance
Theoretical section for drop target
Entered section
Comparison of standard cable sections
Calculation steps
How to calculate voltage drop and compare cable cross-sections
Enter source voltage, current, one-way cable length, wire cross-section and conductor temperature. Compare nominal sizes for DC, single-phase and balanced three-phase circuits. Resistive estimate only: not a cable safety or compliance check.
For 12 V DC, 10 A, a 5 m one-way copper run and 2.5 mm² at 20 °C, drop = 2 × 10 × 0.017241 × 5 / 2.5 = 0.68964 V or about 5.747%. For a 3% target the nominal resistance-only required section is 4.789 mm²; the first size in the available series that meets it is 6 mm².
Results are estimates and depend on the supplied values.
Voltage drop for DC and AC: step-by-step formulas
1. Define circuit type and cable length
DC and single phase include an outgoing and a return conductor, so the resistive drop uses 2. Balanced three-phase uses √3 for line-to-line voltage. Enter only the physical one-way run length.
ΔV (DC/1~) = 2 · I · ρ(T) · L / S; ΔV (3~) ≈ √3 · I · ρ(T) · L / S
2. Adjust resistivity for temperature
Reference resistivity at 20 °C is 0.017241 Ω·mm²/m for IACS copper and 0.028265 for 61% IACS aluminium. Actual commercial conductor values can vary.
ρ(T) = ρ20 × [1 + α × (T − 20 °C)]
3. Calculate voltage drop and percentage
Divide voltage loss by the nominal source voltage. For AC the model assumes an approximately unity power factor and ignores reactance; actual drop may be different.
Drop % = 100 × ΔV / V
4. Estimate a section by voltage drop
Rearrange the formula for S and compare with nominal sizes. This is a voltage drop calculation only and does not verify ampacity or safe installation.
Minimum S = factor × I × ρ(T) × L / (V × target%/100)
5. Calculate resistive losses
DC and single-phase include two current-carrying paths in the resistive loss formula. Balanced three-phase uses three conductors. This is not a thermal safety assessment.
P loss DC/1~ ≈ 2 · I² · ρ(T) · L / S; 3~ ≈ 3 · I² · ρ(T) · L / S
Safety and limitationsThis is an approximate resistance-only model at uniform conductor temperature. AC assumes balanced phase current and near-unity power factor; it neglects reactance, harmonics and neutral effects. It does not assess current-carrying capacity, installation method, grouping, insulation, protection, short-circuit conditions or regulatory voltage-drop limits. The displayed section is NOT a safe installation recommendation or code certification. Actual electrical installation requires qualified professionals applying applicable standards and cable manufacturer specifications. A zero or negative estimated load voltage indicates model breakdown.
Cable voltage drop FAQs
Should I enter the round-trip length?
No. Enter the one-way run length. The model includes the return conductor automatically for DC and single-phase.
Does this work for 12 V or 24 V?
Yes. Choose DC and enter the supply voltage. The percentage drop is particularly important with low voltages.
What about 400 V three-phase?
For a balanced three-phase circuit, enter 400 V line-to-line and select three-phase; the resistive model uses √3.
Why does temperature matter?
Electrical resistivity increases with temperature, increasing voltage drop and resistive losses.
Is the suggested section safe or code compliant?
No. It only meets the modelled drop target. Ampacity, protective devices and code requirements must be assessed separately.
Does this include power factor?
No. It assumes approximately unity power factor and ignores reactance. Inductive loads need more comprehensive calculation.
Should I use the circuit breaker rating as current?
Use the load current relevant to your design scenario; do not substitute a breaker rating without assessing the assumptions.
Can I calculate aluminium conductors?
Yes, using an aluminium reference resistivity, but connections, ampacity and other checks remain outside this tool.